Products/iPAC/Technical Specs



iPAC Home   Technical Specifications   Advanced Features

 

<Back (Pg. 2 of 3) Next>


Measurement Functions

 
  • Voltage and Current RMS Values
  • Neutral Current RMS Values
  • Power Factor Measurement (Power factor correction: Capacitor bank switching)
  • Total Power Measurement
  • Real and Reactive Power Measurement
  • Power Quality Measurement (FFT for Harmonic Measurement)
  • Frequency measurement
  • Total Harmonic Distortion measurement

IEEE Protective Devices

 
  • Sync Check (25)
  • Under Voltage (27)
  • Directional Power (32)
  • Phase Balance (46)
  • Instantaneous Over Current (50)
  • Inverse Time Over Current (51)
  • Over Voltage (59)
  • Voltage Balance (60)
  • Directional (67)
  • Reclosing (79)
  • Under and Over Frequency (81)
  • Lockout (86)
  • Differential for Transformer Protection (87)

Advanced Features for protections

 
  • Coil Monitoring for Relay failure detection.
  • Cold Load Pickup Logic to prevent protective devices from operating when cold load is put on the circuit.
  • Voltage Constraint with Current pickup lowered to increase sensitivity when voltage is also collapsing during the fault.
  • Breaker Control Blocking for coordination with upstream and downstream protective devices via DI or Peer-to-peer communication.
  • Directional on Over Current Devices

Trending and Recording

 
  • Transient disturbance time stamped event recording (External DI, Protective Stage Status and Breaker Operation)
  • AI Wave Form Capture
  • Fault History recording

Communication

 
  • RS232/RS485 ports: 4 user ports, 1 jumper selectable maintenance or user port
  • 4 Sync/Async ports, 1 Async port, 300 – 38.4k Baud
  • Hand shaking signals: DCD, RTS, CTS
  • Specifications: Meet all EIA/TIA-232-E and V.28 Specifications.
  • Multiple Open Protocol support: T101, DNP3, Modbus, CDC II, LG8979
  • Redundant Communication
  • Data Concentrator Protocol: Modbus, IEC T101, DNP 3.0, CDC II

Maintenance

 
  • Window Based DynaView Maintenance Software
  • Window Based DynaConfig Configuration Software

Monitoring and Supervision

 
  • Power Quality Measurement: THD and Harmonic Measurement (up to 32 Harmonics)
  • Electronics temperature Monitoring
  • Circuit Breaker Electric Wear
  • Trip Circuit Supervision (Base on Value of trip coil current, auxiliary Contact of the Trip Relay or the present of the Voltage).
  • Trip/Close Breaker Operation counters
  • Breaker Travel Time Supervision

Control

 
  • Power Factor Control (Capacitor Bank Switching)
  • Programmable Multiple Shots Recloser (Maximum 6 shots)
  • Programmable Digital Output for LED Indications
  • Manual Circuit Breaker control
  • Programmable Logic and Sequential Control

Diagnostics

 
  • Power Up Diagnostics: Software and Configuration Integrity Checking
  • Digital Output Relay Driver Integrity Checking
  • Digital Input Wetting Voltage Monitoring
  • AI Reference Monitoring
  • Battery Voltage Monitoring (Optional)
  • EPROM and RAM integrity Checking

Configuration Template

 
  • Ready made standard configuration or customize the unit to specific application for detail refine setting by customer.

Technology

 
  • CMOS components for low power consumption.
  • Extensive use of Surface Mount components.
  • Employing In-System-Programming technology for EEPROM and EPLD.

CPU, DSP and Memory

 
  • 32- bit HCMOS Motorola 68332 @ 20 MHz.
  • 32- bit Floating Point DSP ADSP21062 @ 40 MHz.
  • CPU Memory: 1 MegaBytes EEPROM. 1 MegaBytes Battery backed up RAM with 3 years of shelf life. Battery can be changed with live power on for uninterrupted operations.
  • DSP Memory: 2 Megabits of on-chip RAM, 128 Kilo-Bytes of Dual Ported RAM.

Real Time Calendar Clock

 
  • Hardware Calendar Clock with year, month, day of month, day of week, hour, minute and second.
  • Optional high accuracy, temperature compensated crystal oscillator, 20.0000 MHz +/- 2 PPM at -20 to 70 degrees Celsius.
  • Battery backed up Real Time Calendar Clock with 3 years of shelf life. Battery can be changed with live power on for uninterrupted operations.

Microprocessor Supervisor

 
  • Watchdog Timer. Power Monitor. Reset. Power Switching functions. Watchdog relay: For system malfunction annunciator, indication and control overrides.

Power Requirement and On-board Power Supplies

 
  • Isolated unregulated 24 VDC (1 Amp) for electronics. Separate Power Supply for Digital Input Excitation.
  • Switching mode, +5 VDC for digital electronic, +5 VDC, -12 VDC and +12 VDC for analog electronic.

System Status Indicators

 
  • Power On indicator. Performance indicator. System normal indicator. Control malfunction indicator.

Digital Inputs

 
  • 16 Optical Isolated Digital Inputs with Input indicator on each digital input.
  • Isolation Rating: 2500 Vrms (Point Input to Logic).
  • Hardware Digital Filter: Programmable 2-15 ms debounce timer, transition detection and interrupt capability.
  • Accumulator: Any digital input can be configured as an Accumulator.
  • Maximum Rate of Accumulator: 150 Hz.
  • Types of point: Form A, Form C and BCD.
  • SOE: Any Digital Input Point can be Configured as SOE with accuracy of 1 ms.
  • Chatter Filter is available for preventing malfunctioning inputs from filling up the SOE buffer.

AC or DC Analog Inputs

 
  • Up to 16 AC Analog Input Points: Can be either Voltage or Current inputs. Rating: I nominal = 5 A or 1 A, V nominal = 120 V, Nominal Frequency: 50/60 Hz
  • Accuracy: +/- 1%
  • Temperature Coefficient: +/-5PPM per degree Celsius.
  • Resolution: 15 bit plus sign.
  • Auto Self Calibration Reference Points: -5.000VDC, 0VDC and +5.000VDC.
  • CMRR (@0-60Hz): 90 dB.
  • NMRR (@60Hz) 60 dB.
  • Analog input self calibration, Auto-correction of gain and offset errors.
  • Up to 16 DC Analog Input Points: Bipolar, Differential input @ +/- 10.0V, +/- 5.0V, +/- 1.0V, +/- 1 mA, +/- 20 mA, 4-20 mA
  • Accuracy: +/- 0.05% (DC voltage input).
  • Temperature Coefficient: +/-5PPM per degree Celsius.
  • Resolution: 15 bit plus sign.
  • Auto Self Calibration Reference Points: -5.000VDC, 0VDC and +5.000VDC.
  • CMRR (@0-60Hz): 90 dB.
  • NMRR (@60Hz) 60 dB.
  • Analog input self calibration, Auto-correction of gain and offset errors.

Digital Outputs

 
  • 16 relay outputs with Output indicator on each digital output.
  • Control Output Configurations: Isolated Discrete control output relays, Trip/Close, Raise/Lower, Set/Reset, Pattern Controls, Relay fail to OFF, Relay fail to last commanded position.
  • Control Security: Single component failure protection, Master Trip/Close relays, relay driver input status check back for point selection confirmation, Double point select-before-operate.
  • Remote/Local Switch for enable/disable controls.
  • Either a Malfunction of the system (detected by the watchdog), or the failure of a point selection confirmation shuts down the control module.
  • Control Functions: ON/OFF, Timed ON/OFF (Pulse Duration of 1 ms resolution), Variable duty cycle pulse output with variable repetition rate (Pulse Train of 1 to 254 or continuous, 1 ms resolution), Pattern controls (a group of contiguous outputs).
  • Contact Rating: 10 Amp at 125 VDC.
  • Dry Contact, 1500 VDC Isolation

Operating Environment

 

Temperature Range: -40 to +85 degrees Celsius. Humidity: < 95%, non-condensing.

 

Advanced Features of iPAC>

<Back (Pg. 2 of 3) Next>

 

© 2003 Dynatrol Systems Inc.  Home  |  Dynatrol  |  Products  |  Services  |  Support  |  Contact  |  Login  |  Privacy Policy